Eco-Energys Bi-Fuel System sophisticatedly, (PLC) control system, which controls both natural gas and diesel fuel during operation. In addition, the PLC System acts as an engine safety device, by monitoring gas and diesel in combustion box. |
|
|
If a fault is detected, the PLC will automatically switch the generator to 100% diesel operation and data-log the fault. The PLC fault set points are field adjustable and allow installation technicians to customize the Bi- Fuel System to the specific requirements of the customer and/or the operational limitations set-forth by the engine manufacturer. Once programmed, the fault settings are protected by a keypad lockout code, which prevents unauthorized personnel from altering the set points.
The PLC guarantees that in the unlikely event of either a Bi-Fuel System malfunction, or a disruption in natural gas supply pressure (either low or high pressure faults), the generator drive-engine will be protected from damage. Most of the monitored channels are latching type faults, i.e. If the Bi-Fuel System is deactivated by the ECS, the generator cannot be returned to Bi-Fuel operation until the PLC panel is manually reset. Lastly, the PLC also incorporates a built-in time delay function, which prevents initiation of Bi-Fuel operation after generator start-up, for a period of up to 300 seconds. This feature is used when the converted generator is used in paralleling operations, and allows the generator to start-up and synchronizes on 100% diesel fuel before automatically switching to Bi-Fuel operation. |
|